GEMC-FW-255KT |
|
255 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
- 24V Panel, 255 Points via commercial addressable, wireless or conventional fire devices, 4 on board NACs providing up to 6.5A notification power
- 7 Amp, 24V Power Supply
- Built in horn/strobe synch. module on each NAC
- Built in dual line communicator; dual onboard serial ports
- Quickloader up/downloading including remote smoke obscuration reporting
- Locking, Large Red Enclosure, 16 x 25” reversible door, with 14.25” x 25” base. Houses up to 32Ah battery backup.
- Menu-driven LCD Fire Keypad mounts anywhere on bus. (Also, full keyswitch support)
|
GEMC-FW-128KT |
|
128 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
As above, but with
- 24V Panel, 128 Points via commercial addressable, wireless or conventional fire devices, 4 on board NACs providing up to 6.5A notification power
|
GEMC-FW-32KT |
|
32 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
Similar to above, but with
- 24V Panel, 32 Points via commercial addressable, wireless or conventional fire devices, 2 on board NACs
- 4 Amp, 24V Power Supply
- Locking, Medium Red Enclosure, 16 x 17” reversible door, with 14.25” x 16” base. Houses up to 16Ah battery backup.
|
Conventional Fire System Peripherals |
GEMC-FK1 |
|
- LCD Fire Red Keypad (Menu-driven operation, functionality for Reset, Acknowledge, Silence (with disable).
|
GEMC-F8ZCPIM |
|
- Conventional 8-zone 2-wire fire input module. Plugs into motherboard, for conventional 2-wire smoke detectors or any conventional fire detection device.
|
GEMC-EZM8 |
|
|
GEMC-NL-MOD |
|
- Internet Reporting Module
|
Wireless Firewolf Peripherals |
GEMC-WL-SMK |
|
- Gemini Comml Wireless Smoke, Photoelectric
|
GEMC-WL-HEAT |
|
- Gemini Comml Wireless Heat, 135º F
|
GEMC-WL-WD2 |
|
- Gemini Comml Wireless 2-input module
|
GEMC-REVC |
|
- Gemini Commercial Wireless 255 point RF Receiver (Up to 4 per system, max.)
|
Addressable Firewolf Peripherals |
GEMC-FW-SLC |
|
- Addressable SLC Fire Module, supports up to 128 addressable SLC fire devices, below. Up to 2 connect to Panel.
|
FWC-FSLC-SMK |
|
- Addressable Analog SLC Smoke, photoelectric, head**
|
FWC-FSLC-HEAT |
|
- Addressable Analog SLC Heat, 135ºF, head**
|
FWC-FSLC-DUCT |
|
- Addressable SLC Duct smoke detector, photoelectric
|
FWC-FSLC-DUCTRA |
|
- Remote Indicator Plate with LED indicator & key reset.
|
FWC-FSLC-EZM2 |
|
- Addressable SLC 2-zone conventional expansion module. Uses one address on SLC loop, but yields 2 indep. contact monitoring circuits, for pull stations, water flow and other dry contact alarm initiating devices.
|
FWC-FSLC-EZM1 |
|
- Addressable SLC 1-input conventional module, similar to usage above.
|
FWC-FSLC-CZM |
|
- Addressable SLC single module, for montoring of dry contacts, ie., pull stations and conv. smokes
|
FWC-FSLC-RM2 |
|
- Addressable SLC 2-output module (requires 1 SLC address)
|
FWC-FSLC-ISO |
|
- Addressable SLC Short Circuit Module (Optional: For special applications, meets Class A, Style 7 loop reqts.)
|
FWC-FSLC-SOM1 |
|
- Addressable SLC Fire supervised output module. Application examples: elevator recall, HVAC shutdown, add’l NAC output w/ power supply
|
FWC-FSLC-PULL |
|
- Addressable SLC Fire Pull Station
|
| FWC-FSLC-PULLK |
|
- Version of above, with key reset.
|
| FWC-FSLC-PULL2 |
|
- Dual action pull station, with hex-key reset.
|
| FWC-FSLC-PULL2K |
|
- Dual action, with key reset.
|
FWC-FSLC-PROG2 |
|
- Tool for address-programming SLC devices
|
FWC-FSLC-SMK6B |
|
- ** Smoke/Heat 6" Base, required for FWC-FSLC- SMK and –HEAT devices
|
Output Options |
GEMC-NAC7 |
|
- Remote 4-output NAC Extender, for 6.5A ttl, or 2A, max. on any 1 output. Red 14 x 16” can, connects to 120VAC, supports 32Ah standby batts. Supervised, fire bus connection. System Sensor and Wheelock NAC synch. (5/system, for 20 add’l NAC circuits ttl.)
|
GEMC-12V2APS-CF |
|
- 12VDC Power Supply for Fire Bus, remote supervised. Direct 120VAC connection, supports 2ea. 12V, 7Ah standby batts.
|
GEMC- FPRINT |
|
|
GEMC-RM3008 |
|
- 8 Form C Relay Output Module
|
GEMC-RS232 |
|
- RS232 Adapter for serial output from Panel
|
GEMC-OUT8 |
|
- PGM Output Module, 8 open collector PGM outputs
|
New Options |
| GEMC-KEYSWKIT Keyswitch Kit |
|
- To be used in cases where it is required that a keyswitch be used to unlock the fire keypad. The GEMC-KEYSWKIT consists of an easy-to-install keypad / keyswitch mounting box that allows codeless locking and unlocking of the Napco GEM-FK1 Fire alarm keypad. The GEMC-KEYSWKIT is designed to be mounted to a one, two or three-gang electrical box, or to a hollow wall using mounting hardware appropriate for the mounting surface. The keyswitch is wired into one of two existing GEMC-FK1 keypad inputs; when the key is inserted and rotated, the keyswitch closes, triggering a keypad command to the control panel to unlock that keypad.
- This feature may be configured to allow either a maintained or momentary keyswitch closure to unlock the keypad for a 15 minute period OR a maintained keyswitch closure which will unlock the keypad when opened will lock the keypad when closed
|
| GEMC-LOCK-CAT30 Key-Alike |
|
- To be used in cases where it is required that the same key used to reset the pull stations also be used to unlock the control panel enclosure. Simply replace the standard enclosure lock with the GEMC-LOCK-CAT30 to "key alike" the pull station and enclosure lock. Note - the GEMC-KEYSWKIT, above is also keyed to CAT 30, allowing one key to unlock the keypad, reset the pull stations and open the GEMC control panel enclosure.
|
| FN-CTM City Tie Module |
|
- The FN-CTM is a City Tie Module used to connect the GEMC Fire Alarm Control Panel to a Local Energy type City Tie Monitoring circuit. The FN-CTM City Tie Module circuit provides the power necessary to trip the Master Box Trip Coil when the Fire Alarm Control Panel goes into alarm. The City Tie Circuit is capable of providing 1A for 0.5 seconds to operate the Master Box Trip Coil. The wiring is supervised to the Master Box by placing the EOL resistor device on the terminals of the FN-CTM City Tie Module.
|